FP900

Perkins FullAlternator Leroy Somer
CEbelgesi TSE ISO140012015 ISO90012015 ISO450012018 EAC Made In Türkiye

FULL 900 KVA DIESEL GENERATOR PERKINS ENGINE

FULL 900 KVA PERKINS ENGINE DIESEL GENERATOR

Stand By (kVA)
900 Kilovolt-Ampere
Stand By (kW)
720 Kilowatt
Prime (kVA)
818
Prime (kW)
655 Kilowatt
Rated Current (A)
1178
Frequency
50 Hertz
PDF Get a Quote
Engine
Engine Brand PERKINS
Engine Model 4006-23TAG3A
Number and Type of Cylinders 6 Inline
Injection and System Type Direkt
Compression Ratio 13.6:1
Diameter 160 Millimetre
Stroke 190 Millimetre
Cylinder Displacement 22.9 Litre
Air Suction Power Turbocharged & Air To Air Charge Cooled
Rotational Speed 1500 Revolutions per Minute
Crankcase Oil Capacity (Lt) 114 Litre
Standby Power 786 / 1053
Prime (PRP) 705 / 945
Fuel Type Euro Diesel
Governor System Mechanical
Cooling Method Water Cooled
Coolant Capacity 105 Litre
Fuel Consumption at Full Load 172 Litre
Fuel Consumption at 75% Load 130 Litre
Fuel Consumption at 50% Load 90 Litre
Alternator
Frequency (Alternator) 50 Hertz
Voltage 400 Volt
Phase 3
Voltage Regulation ±1%
Insulation Class H
Protection Class IP23
Power Factor 0.8 Ratio
Dimensions
Weight With/Without Cabin 8200 (6400) Kilogram
Width (mm) - With/Without Cab 2300 (2300) Millimetre
Length (mm) - With/Without Cab 6000 (6000) Millimetre
Height (mm) - With/Without Cabin 3385 (3385) Millimetre
Fuel Tank Capacity 1600 Litre
FULL 900 KVA PERKINS ENGINE DIESEL GENERATOR
0
Product Comparison